| BUSINESS ADDRESS |
|
BSMC POWER Nigeria Limited
|
|
3rd Floor- Society of Nigerian Engineers Building,
No.1, Engineering Close,
Off Idowo Taylor Street,
Victoria Island, Lagos (Nigeria)
GSM:+234-8020969082
+234-8026876251
|
| | | |
| |
| BSMC Power Nigeria Limited |
Specialized in Supply,Installation, Commissioning & Maintenance of : |
|
|
|
| | | |
| | |
 |
BSM I - 1500 W 1U Compact Inverter | |
 |
- Versatile modular design provides flexibility for different power applications
- Expandable capacity up to 24KVA with N+1 redundancy configuration
- All master” dynamic mechanism eliminates single point failure to optimize reliability
- Hot-pluggable operation allows module addition or removal without powering down
- High power density and high efficiency (89%)
|
| |
INEX inverter series is an integrated
Telecommunication Power System,
including inverter, static switch, LCD display
controller, and interface modules. With
versatile “building block” design and N+1
redundant configuration, the INEX inverter
system facilitates complex telecommunication
and industrial power demands, and provides
ultimate flexibility for your current and
future power requirements. |
| |
N+1 parallel redundancy allows
power capacity expandable up to 24KVA. INEX
"all master" dynamic mechanism automatically
shares and re-organizes critical loads to
prevent interruption should any inverter
module fail. The DSP-microprocessing controller
gives real-time system status through comprehensive
LCD display, and allows program settings
through the display panel. With a communication
interface module installed, you can further
control and monitor the system remotely.
BSMC POWER
NIGERIA - Leading Manufacturers, Suppliers
and Exporters of Telecom Inverters, Telecommunication
Power Systems, Telecom Power Monitoring
Systems. |
[Manufacturers, exporters, suppliers and wholesalers
of Telecom Inverters]
|
| Inverter Module |
INEX inverter module provides pure sine wave AC
power output for critical telecommunication equipment.
Adopting N+1 redundancy design, INEX Inverter can
operate up to 24 units in parallel. INEX inverter module
is specially designed with compact size of maximized
power density and can reach up to 5.57W/inch3 for INEX
1000 and 8.36W/inch3 for INEX1500. 1U height design
allows the module to be installed onto a standard ETSI
300mm Rack. INEX module provides the revolutionary
telecom power solution in terms of maximum flexibility
and reliability. |
 |
- Pure sine wave
- Hot-swap replacement in
shelf
- High efficiency >89%
- DSP design for higher
system reliability
- Lower audible noise
<55dBA
- Smart fan speed control
- N+1 redundancy system,
load sharing difference < 5%
-
High power density
- Emergency Power Off
function embedded
- CAN Bus interface
embedded
- -48Vdc Telecom system
application
- Wide operation temperature range, -20˚C to 70˚C
|
|
|
[Manufacturers, exporters,
suppliers and wholesalers of Telecom Inverters] |
| STS Module |
INEX STS (Static Transfer Switch) module increases system reliability by automatic power transfer between the inverter output and the AC mains. By setting up the priority of operation mode, users can change the system status of “on line mode” or “off line mode”. The on line mode will keep the input power provided by inverter line and when inverter fails, the line will switch to AC utility line. In off line mode, the system power is always connected to the AC utility line and will switch to inverter power line when AC utility fails. The transfer time is less than 1/4 cycle which prevents the power interruption. The reliable performance of INEX STS module will provide the maximum protection to the connected telecommunication equipment against possible damage caused by the system power failure. |
 |
- Universal input range
- Hot-swap replacement in shelf
- Back-feed protection
- Redundant fan design
- Redundant power supply
design
- Operation Priority
Setup of transfer side by setting in Control
Module
- Fast transfer time,
typically less than 1/4 cycle
- Wide operation
temperature range, -20˚C to 70˚C
- Lower audible noise
<55dBA
- Emergency Power Off
function embedded
- No-cross connect
- Optional maintenance
bypass switch function
- CAN Bus interface embedded
|
|
| |
| Controller Module |
INEX controller module allows users to monitor the system status in real time. The superior design enables users to manage the inverter and STS module status including voltage, current, frequency, capacity and temperature. With a user-friendly interface design, users can easily manage the inverter and STS module settings including voltage, frequency, redundancy (for inverter module), and priority (STS module). The controller module can also record the alarm history which can help to understand the operating status while maintaining the system or making further adjustments to improve system performance. |
 |
- CAN Bus protocol for
module communication
- Relay contact output
for customized alar ms
- Hot swappable design
- Real time clock
embedded
- Comprehensive LCD &
LED for status display
- Audible alarm function
|
|
|
[Manufacturers, exporters,
suppliers and wholesalers of Telecom Inverters] |
| Communication Interface |
The communication interface includes several options for wider applications which facilitates the remote managing to the system. The standard ports include relay contacts, RS-232, RS-485, USB. Relay contacts provide five programmable settings to display customized infor mation. RS-232 & USB ports provide the serial connection to PC for software monitoring. RS-485 provides long distance connection for direct monitoring. The optional SNMP offers remote monitoring capability using a browser interface. The communication interface provides powerful monitoring and managing solutions to the system manager. |
 |
- Relay contacts
- RS-232
- RS-485
- SNMP (Optional)
- USB
|
|
| |
|
Telecom Power
Monitoring Software |
TelecomPower is a monitoring software which supports
either stand alone computer or network connected
computers. |
 |
- Monitoring to each
module in the inverter system in real time.
-
Provides panoramic view
of all the related information of utility power,
system status, STS status
- Auto search function
with any inver ter power modules in LAN.
- Password security
protection
- Install and uninstall is easy and clear
|
|
| |
|
Inex System 48V Modular Inverter System |
|
[Manufacturers, exporters,
suppliers and wholesalers of Telecom Inverters] |
|
Electrical |
|
Inverter Module |
| DC input |
Nominal voltage: 48VDC
Operating range: 40.5VDC ~ 58VDC
Input protection: Reverse Polarity Protection
Psophometric noise voltage: ≤1.0mV ITU-T O.41 (16.66~6000Hz) |
| |
| AC output |
Power Rating: 1000VA/800W, 1500VA/1200W
Waveform: Pure Sine Wave
Power factor: 0.8
Nominal output voltage: 110/115/120Vac, 208/220/230/240Vac
Voltage variation: Max ±2%
Output frequency: 50/60Hz
Crest factor: 3:1
THD: <3%, linear load
<5%, non-linear load
Efficiency: Min 89%
Isolation AC-Enclosure: Basic isolation (Pri-Gnd) 2121Vdc/1min
Dynamic Response: <±10%
Over Load Protection: 1.5*Inom >20s
1.25*Inom temperature controlled |
| |
|
STS Module |
| Input |
|
Over voltage threshold: |
Adjustable between
127 to 138Vac for 120Vac systems,
the default value is 132Vac
233 to 252Vac for 220Vac systems,
the default value is 242Vac |
| Under voltage threshold: |
Adjustable between
100 to 114Vac for 120Vac systems,
the default value is 108Vac
176 to 209Vac for 220Vac systems,
the default value is 198Vac |
| Backfeed Protection:
|
Comply with safety requirement |
| Redundant Power: |
Startup power-on by priority |
| Design: |
Source or alternative |
| |
|
| Output |
|
| Nominal Output Voltage:
|
Same as utility or the output of Inverter modules |
| Permissible Frequency Area:
|
Max. +/-2.5% (inverter synchronization) |
| Transfer Time:
|
Typical 1/4cycle |
| Rated Power:
|
50A for 110/115/120Vac & 208/220/230/240Vac |
| Operation Methods:
|
Inverter priority/Mains priority |
|
| |
|
| Environmental |
|
Operating Temperature: - |
-20°C to 70°C (-4° to 158°F) -5°C to 58°C (23° to 122°F)
with full performance |
| Storage Temperature: |
-40°C to +85°C (-40° to 185°F) |
| Humidity:
|
90% Relative Humidity (non condensing) |
| Audible Noise:
|
55dB |
|
| |
|
Controller Module |
|
Input |
|
| Nominal voltage:
|
48VDC |
| Operating range:
|
30VDC ~ 72VDC |
| Over Current
|
Protection: 2A Fuse |
| |
|
|
Human Interface |
|
| LCD: |
Resolution (Line X Array) 4 X 16 Charactor |
| LED Indicator:
|
3 colored indicators for normal, warning and fault display |
| Alarm: |
Audio alarm when inverter, STS, controller module operate abnormally |
| |
|
|
System Parameter |
|
| BaudRate:
|
Setting controller com port baud rate |
| Keypad tones:
|
Setting keypad tones |
| Time & Date:
|
Setting current time and date |
| Setting Password:
|
Setting system password |
| Brightness:
|
Setting LCD brightness |
| Default: |
Change current system parameters to default value |
| Battery Calibration:
|
Calibration battery voltage |
|
| |
|
Mechanical |
|
Inverter Module |
|
| Dimension |
|
| mm:
|
270D x 215W x 43.8H |
| inches: |
10.63D x 8.46W x 1.72H |
| Weight: |
2.5kg (5.5lb) |
|
|
STS Module |
|
| Dimension |
|
| mm:
|
270D x 215W x 43.8H |
| inches: |
10.63D x 8.46W x 1.72H |
| Weight: |
2.0kg (4.4lb) |
|
|
Controller Module |
|
| Dimensions (D x W x H): |
|
| mm:
|
277D x 87.9W x 43.5H |
| inches: |
10.9D x 3.46W x 1.71H |
| Weight: |
1.0kg (2.2lb) |
|
|
Hot-swap Chassis |
|
19/23” mounting brackets
Inverter Chassis
Dimension |
|
| mm:
|
320D x 440W x 44H |
| inches: |
12.6D x 17.32W x 1.73H |
| Weight: |
2.5kg (5.5lb) |
|
|
STS & Controller Chassis |
|
| Dimension |
|
| mm:
|
320D x 440W x 44H |
| inches: |
12.6D x 17.32W x 1.73H |
| Weight: |
3.4kg (7.5lb) |
|
| |
|
Communication Interface |
RS-232×1: Communicate with PC
RS-485×2: Communicate with supervision
Dry Contact×5: Communicate with external Monitor
USB×1: Communicate with PC |
| |
|
Standards |
| UL, CE, RoHS |
| |
|
| |
|
| |
| |
|
|
|
|
| |